Normal Recharge: Batteries to be recharged in CC-CV mode only | ||
Mode of operation | Voltage setting per 12V unit for amount temperature 20-30 C | Current setting |
Float | 13.7V +/- 0.1V | Maximum: 0.2 CA Minimum: 0.1 CA |
Cyclic | 14.7V +/- 0.1V | |
Temperature Compensation: (Reference 25 degree Celcius) Float: 18 mV/ degree Celcius/ 12V unit Cyclic: 30 mV/ degree Celcius/ 12V |