Application Chart for Exide Invamore Batteries

Normal Recharge: Batteries to be recharged in CC-CV mode only
Mode of operation Voltage setting per 12V unit for amount temperature 20-30 C Current setting
Float 13.7V +/- 0.1V Maximum: 0.2 CA

Minimum: 0.1 CA
Cyclic 14.7V +/- 0.1V

Temperature Compensation: (Reference 25 degree Celcius)

Float: 18 mV/ degree Celcius/ 12V unit

Cyclic: 30 mV/ degree Celcius/ 12V